Application Guide | iC2-Micro Frequency Converters
P 6.1.3 Running Hours
Use this parameter to view how many hours the motor has run. Reset the counter with P 6.1.9 Reset Running Hours Counter. The value is
saved when the drive is turned off.
Default value: 0 Parameter type: Range (0–2147483647)
Parameter
number:
1501 Unit: h
Data type: uint32 Access type: Read
P 6.1.4 kWh Counter
Register the power consumption of the motor as an average value over 1 hour. Reset the counter in P 6.1.8 Reset kWh Counter.
Default value: 0 Parameter type: Range (0–2147483647)
Parameter
number:
1502 Unit: kWh
Data type: uint32 Access type: Read
P 6.1.5 Power Up's
Use this parameter to view the number of times the frequency converter has been powered up.
Default value: 0 Parameter type: Range (0–2147483647)
Parameter
number:
1503 Unit:
Data type: uint32 Access type: Read
P 6.1.6 Over Temp's
Use this parameter to view the number of frequency converter temperature faults that have occurred since production.
Default value: 0 Parameter type: Range (0–65535)
Parameter
number:
1504 Unit:
Data type: uint16 Access type: Read
P 6.1.7 Over Volt's
Use this parameter to view the number of frequency converter overvoltages that have occurred since production.
Default value: 0 Parameter type: Range (0–65535)
Parameter
number:
1505 Unit:
Data type: uint16 Access type: Read
P 6.1.8 Reset kWh Counter
Use this parameter to reset the kWh counter to zero (see P 6.1.4 kWh Counter).
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 189