EasyManuals Logo

Danfoss iC2 User Manual

Danfoss iC2
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #224 background imageLoading...
Page #224 background image
Selection number Selection name Selection description
0 No Operation No reaction to signals transmitted to the terminal.
1 Reset Resets the frequency converter after a trip/alarm. Not all alarms
can be reset.
2 Coast Inverse Coasting stop, inverted input (NC). The frequency converter
leaves the motor in free mode. Logic 0coasting stop.
3 Coast and Reset Inverse Reset and coasting stop inverted input (NC). Leaves motor in free
mode and resets frequency converter. Logic 0coasting stop.
Logic 1 to Logic 0reset.
4 Quick Stop Inverse Inverted input (NC). Generates a stop in accordance with the
quick stop ramp time set in P 5.7.7 Quick Stop Ramp Time. When
the motor stops, the shaft is in free mode. Logic 0Quick-stop.
5 DC-brake Inverse Inverted input for DC braking (NC). Stops the motor by
energizing it with a DC current for a certain time period. See
P 5.7.4 DC Brake Current to P 5.7.5 DC Brake Frequency. The
function is only active when the value in P 5.7.3 DC Brake Time is
different from 0. Logic 0DC braking.
6 Stop Inverse Stop inverted function. Generates a stop function when the
selected terminal goes from logic 1 to logic 0. The stop is
performed according to the selected ramp time (P 5.5.4.9 Ramp 2
Accel. Time and P 5.5.4.10 Ramp 2 Decel. Time).
Note: When the frequency converter is at the torque limit and
has received a stop command, it may not stop by itself. To ensure
that the frequency converter stops, configure a digital output to
[27] Torque limit and stop and connect this digital output to a
digital input that is configured as coast.
8 Start Select start for a start/stop command. Logic 1=start, logic 0=stop.
9 Latched Start The motor starts when a pulse is applied for minimum 4 ms. The
motor stops when stop commands are given.
10 Reversing Change the direction of motor shaft rotation. Select logic 1
to reverse. The reversing signal only changes the direction of
rotation. It does not activate the start function. Select both
directions in P 5.8.1 Rotation Direction. The function is not active
in process closed loop.
11 Start Reversing Used for start/stop and for reversing on the same wire. Signals on
start are not allowed at the same time.
12 Enable Start Forward Disengage the counterclockwise movement and allows for the
clockwise direction.
13 Enable Start Reverse Disengage the clockwise movement and allows for the
counterclockwise direction.
14 Jog Use to activate jog speed. See P 5.9.2 Jog Reference 1.
224 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss iC2 and is the answer not in the manual?

Danfoss iC2 Specifications

General IconGeneral
BrandDanfoss
ModeliC2
CategoryMedia Converter
LanguageEnglish

Related product manuals