40% duty cycle, vertical braking, T2
FC 202 Vertical braking 40% duty cycle
Adjustable frequency drive data
Brake resistor data Installation
R
rec
[Ω]
P
br,cont.
[kW (hp)]
Danfoss part number Cable
cross-
section
[mm
2
(AWG)]
Thermo
relay
[A]
Line
power
type
P
m
[kW
(hp)]
R
min
[Ω]
R
br,nom
[Ω]
Wire IP54
Screw
terminal
IP21
Screw
terminal
IP65
Bolt
connection
IP20
T2
0.25
(0.34)
380 691.3 630
0.100
(0.134)
175u3002 - - - 1.5 (16) 0.4
T2 0.37 (0.5) 380 466.7 410
0.100
(0.134)
175u3004 - - - 1.5 (16) 0.5
T2
0.55
(0.75)
275 313.7 300
0.200
(0.268)
175u3096 - - - 1.5 (16) 0.8
T2 0.75 (1.0) 188 230.0 200
0.200
(0.268)
175u3008 - - - 1.5 (16) 0.9
T2 1.1 (1.5) 130 152.9 145
0.300
(0.402)
175u3300 - - - 1.5 (16) 1.3
T2 1.5 (2) 81.0 110.5 100
0.450
(6.032)
175u3301 175u3402 175u3401 - 1.5 (16) 2
T2 2.2 (3) 58.5 74.1 70
0.570
(0.764)
175u3302 175u3404 175u3403 - 1.5 (16) 2.7
T2 3 (4) 45.0 53.7 48
0.960
(12.869)
175u3303 175u3406 175u3405 - 1.5 (16) 4.2
T2 3.7 (5) 31.5 39.9 35
1.130
(1.515)
175u3304 175u3408 175u3407 - 1.5 (16) 5.4
T2 5.5 (7.5) 22.5 28.7 27
1.400
(1.877)
175u3305 175u3410 175u3409 - 1.5 (16) 6.8
T2 7.5 (10) 17.7 20.8 18
2.200
(2.949)
175u3306 175u3412 175u3411 - 1.5 (16) 10.4
T2 11 (15) 12.6 14.0 13
3.200
(4.289)
175u3307 175u3414 175u3413 - 2.5 (14) 14.7
T2 15 (20) 8.7 10.2 9.0
5.500
(7.373)
- 175u3176 175u3177 - 4 (12) 23
T2 25 (18.5) 5.3 8.2 5.7
6.000
(8.043)
- - - 175u3233 10 (8) 33
T2 22 (30) 5.1 6.9 5.7
8.000
(10.724)
- - - 175u3234 10 (8) 38
T2 30 (40) 3.2 5.0 3.5
9.000
(12.064)
- - - 175u3235 16 (6) 51
T2 37 (50) 3.0 4.1 3.5
14.000
(18.767)
- - - 175u3224 25 (4) 63
T2 45 (60) 2.4 3.3 2.8
17.000
(22.788)
- - - 175u3227 35 (2) 78
Table 6.8 T2, Vertical Braking 40% Duty Cycle, Recommended Brake Resistors