FC 202 Vertical braking 40% duty cycle
Adjustable frequency drive data
Brake resistor data Installation
R
rec
[Ω]
P
br,cont.
[kW (hp)]
Danfoss part number Cable
cross-
section
[mm
2
(AWG)]
Thermo
relay
[A]
Line
power
type
P
m
[kW
(hp)]
R
min
[Ω]
R
br,nom
[Ω]
Wire IP54
Screw
terminal
IP21
Screw
terminal
IP65
Bolt
connection
IP20
T4
160
(225)
2.5 3.6 3.3
60.000
(80.429)
- - - 175u3225
2 x 35 (2 x
1)
135
T4
200
(275)
2.0 2.9 2.7
78.000
(104.558)
- - - 175u3228
2 x 50
(2x1)
170
T4
250
(350)
1.6 2.3 2.1
90.000
(120.643)
- - - 175u3230
2 x 70 (2 x
3/0)
207
T4
315
(425)
1.2 1.8 1.7 - - - - - - -
T4
355
(475)
1.2 1.6 1.3 - - - - - - -
T4
400
(550)
1.2 1.4 1.2 - - - - - - -
T4
450
(600)
1.1 (1.5) 1.3 1.1 (1.5) - - - - - - -
T4
500
(650)
0.9 1.1 (1.5) 2 x 1.9 - - - - - - -
T4
560
(750)
0.9 1.0 2 x 1.7 - - - - - - -
T4
630
(850)
0.8 0.9 2 x 1.5 - - - - - - -
T4
710
(950)
0.7 0.8 2 x 1.3 - - - - - - -
T4
800
(1075)
0.6 0.7 3 x 1.8 - - - - - - -
T4
1000
(1350)
0.5 0.6 3 x 1.6 - - - - - - -
Table 6.10 T4, Vertical Braking 40% Duty Cycle, Recommended Brake Resistors
Type code and Selection Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 133
6 6