40% duty cycle, vertical braking, T6
FC 202 Vertical braking 40% duty cycle
Adjustable frequency drive data
Brake resistor data Installation
R
rec
[Ω]
P
br,cont.
[kW (hp)]
Danfoss part number Cable
cross-
section
[mm
2
(AWG)]
Thermo
relay
[A]
Line
power
type
P
m
[kW
(hp)]
R
min
[Ω]
R
br,nom
[Ω]
Wire IP54
Screw
terminal
IP21
Screw
terminal
IP65
Bolt
connection
IP20
T6 0.75 (1.0) 620 1329.7 1200
0.360
(0.483)
- 175u3102 175u3103 - 1.5 (16) 0.6
T6 1.1 (1.5) 620 889.1 850
0.280
(0.375)
175u3317 175u3104 175u3105 - 1.5 (2) 0.6
T6 1.5 (16) 550 642.7 570
0.450
(6.032)
175u3318 175u3430 175u3429 - 1.5 (16) 0.9
T6 2.2 (3) 380 431.1 415
0.570
(0.764)
175u3319 175u3432 175u3431 - 1.5 (16) 1.1 (1.5)
T6 3 (4) 260 312.5 270
0.960
(12.869)
175u3320 175u3434 175u3433 - 1.5 (16) 1.8
T6 4 (5) 189 231.6 200
1.130
(1.515)
175u3321 175u3436 175u3435 - 1.5 (16) 2.3
T6 5.5 (7.5) 135 166.6 145
1.700
(2.279)
175u3322 175u3126 175u3127 - 1.5 (16) 3.3
T6 7.5 (10) 99.0 121.1 100
2.200
(2.949)
175u3323 175u3438 175u3437 - 1.5 (16) 4.4
T6 11 (15) 69.0 81.6 72
3.200
(4.289)
175u3324 175u3440 175u3439 - 1.5 (16) 6.3
T6 15 (20) 48.6 59.4 52
5.500
(7.373)
- 175u3148 175u3149 - 1.5 (16) 9.7
T6 25 (18.5) 35.1 47.9 38
6.000
(8.043)
- - - 175u3239 2.5 (14) 12.6
T6 22 (30) 27.0 40.1 31
8.000
(10.724)
- - - 175u3240 4 (12) 16
T6 30 (40) 22.5 29.2 27
10.000
(13.405)
- - - 175u3200 4 (12) 19
T6 37 (50) 17.1 23.6 19
14.000
(18.767)
- - - 175u3204 10 27
T6 45 (60) 13.5 19.4 14
17.000
(22.788)
- - - 175u3207 10 (8) 35
T6 55 (75) 11.7 15.8 13.5
21.000
(28.150)
- - - 175u3208 16 (6) 40
T6 75 (100) 9.9 11.5 11
26.000
(34.853)
- - - 175u3211 25 (4) 49
T6 90 (125) 8.6 9.6 7.0
30.000
(40)
- - - 175u3241 35 66
Table 6.12 T6, Vertical Braking 40% Duty Cycle, Recommended Brake Resistors
Type code and Selection
Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 135
6 6