FC 202 Horizontal braking 10% duty cycle
Adjustable frequency drive data
Brake resistor data Installation
R
rec
[Ω]
P
br,cont.
[kW (hp)]
Danfoss part number Cable
cross-
section
[mm
2
(AWG)]
Thermo
relay
[A]
Line
power
type
P
m
[kW
(hp)]
R
min
[Ω]
R
br,nom
[Ω]
Wire IP54
Screw
terminal
IP21
Screw
terminal
IP65
Bolt
connection
IP20
T7
315
(425)
2.3 3.7 3.2
26.000
(34.853)
- - - 175u3085 50 (1/0) 90
T7
400
(550)
2.3 2.9 2.5
32.000
(42.895)
- - - 175u3089 70 (3/0) 113
T7
450
(600)
2.0 2.6 2.3
36.000
(48.257)
- - - 175u3090
2 x 35 (2 x
1)
125
T7
500
(650)
1.9 2.3 2.0
42.000
(56.300)
- - - 175u3092
2 x 35 (2 x
1)
145
T7
560
(750)
1.5 2.1 1.6
52.000
(69.705)
- - - 175u3094
2 x 50
(2x1)
180
T7
630
(850)
1.4 1.8 1.4
60.000
(80.429)
- - - 175u3095
2 x 50
(2x1)
207
T7
710
(950)
1.2 1.6 2 x 2.6 - - - - - - -
T7
800
(1075)
1.1 (1.5) 1.4 2 x 2.2 - - - - - - -
T7
900
(1200)
1.0 1.3 2 x 2.0 - - - - - - -
T7
1000
(1350)
0.9 1.1 (1.5) 3 x 2.6 - - - - - - -
T7
1200
(1600)
0.8 1.0 3 x 2.4 - - - - - - -
T7
1400
(1875)
0.6 0.8 3 x 2.0 - - - - - - -
Table 6.13 T7, Horizontal Braking 10% Duty Cycle, Recommended Brake Resistors
Type code and Selection Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 137
6 6