40% duty cycle, vertical braking, T7
FC 202 Vertical braking 40% duty cycle
Adjustable frequency drive data
Brake resistor data Installation
R
rec
[Ω]
P
br,cont.
[kW (hp)]
Danfoss part number Cable
cross-
section
[mm
2
(AWG)]
Thermo
relay
[A]
Line
power
type
P
m
[kW
(hp)]
R
min
[Ω]
R
br,nom
[Ω]
Wire IP54
Screw
terminal
IP21
Screw
terminal
IP65
Bolt
connection
IP20
T7 1.1 (1.5) 620 830 630
0.360
(0.483) - 175u3108 175u3109 - 1.5 (16) 0.8
T7 1.5 (2) 513 600 570
0.570
(0.764) - 175u3110 175u3111 - 1.5 (16) 1
T7 2.2 (3) 340 403 415
0.790
(1.059) - 175u3112 175u3113 - 1.5 (16) 1.3
T7 3 (4) 243 292 270
1.130
(1.515) - 175u3118 175u3119 - 1.5 (16) 2
T7 4 (5) 180 216 200
1.700
(2.279) - 175u3122 175u3123 - 1.5 (16) 2.8
T7 5.5 (7.5) 130 156 145
2.200
(2.949) - 175u3106 175u3107 - 1.5 (16) 3.7
T7 7.5 (10) 94 113 105
3.200
(4.289) - 175u3132 175u3133 - 1.5 (16) 5.2
T7 11 (15) 94.5 110.9 105
4.200
(5.630)
- 175u3134 175u3135 - 1.5 (16) 6
T7 15 (20) 69.7 80.7 72
4.200
(5.630)
- 175u3142 175u3143 - 1.5 (16) 7.2
T7 25 (18.5) 46.8 65.1 52
6.000
(8.043)
- - - 175u3242 2.5 (14) 10.8
T7 22 (30) 36.0 54.5 42
8.000
(10.724)
- - - 175u3243 2.5 (14) 13.9
T7 30 (40) 29.0 39.7 31
10.000
(13.405)
- - - 175u3244 4 (12) 18
T7 37 (50) 22.5 32.1 27
14.000
(18.767)
- - - 175u3201 10 (8) 23
T7 45 (60) 18.0 26.3 22
17.000
(22.788)
- - - 175u3202 10 (8) 28
T7 55 (75) 13.5 21.4 15.5
21.000
(28.150)
- - - 175u3205 16 (6) 37 (50)
T7 75 (100) 13.5 15.6 13.5
26.000
(34.853)
- - - 175u3209 16 (6) 44
T7 90 (125) 8.8 13.0 11
36.000
(48.257)
- - - 175u3212 25 (4) 57
T7
110
(150)
8.8 10.6 9.1
42.000
(56.300)
- - - 175u3214 35 (2) 68
T7
132
(175)
6.6 8.8 7.4
52.000
(69.705)
- - - 175u3215 50 (1/0) 84
T7
160
(225)
4.2 7.2 6.1
60.000
(80.429)
- - - 175u3218 70 (3/0) 99
T7
200
(275)
4.2 5.8 5.0
78.000
(104.558)
- - - 175u3220
2 x 35 (2 x
1)
125
T7
250
(350)
3.4 4.6 4.0
90.000
(120.643)
- - - 175u3222
2 x 35 (2 x
1)
150
Type code and Selection
VLT
®
AQUA Drive FC 202
138 Danfoss A/S © 09/2014 All rights reserved. MG20N622
66