EasyManuals Logo

Danfoss VLT AQUA Drive FC 202 Design Guide

Danfoss VLT AQUA Drive FC 202
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #159 background imageLoading...
Page #159 background image
Type designation P37K P45K P55K P75K P90K
High/normal overload
1)
HO NO HO NO HO NO HO NO HO NO
Typical shaft output [kW] 30 37 37 45 45 55 55 75 75 90
Typical shaft output at 460 V [hp] 40 50 50 60 60 75 75 100 100 125
Protection rating IP20/Chassis
6)
B4 C3 C3 C4 C4
Protection rating IP21/Type 1 C1 C1 C1 C2 C2
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
C1 C1 C1 C2 C2
Output current
Continuous (3x380–440 V) [A] 61 73 73 90 90 106 106 147 147 177
Intermittent (60 s overload) (3x380–
440 V) [A]
91.5 80.3 110 99 135 117 159 162 221 195
Continuous (3x441–480 V) [A] 52 65 65 80 80 105 105 130 130 160
Intermittent (60 s overload) (3x441–
480 V) [A]
78 71.5 97.5 88 120 116 158 143 195 176
Continuous kVA at 400 V [kVA] 42.3 50.6 50.6 62.4 62.4 73.4 73.4 102 102 123
Continuous kVA at 460 V [kVA] 41.4 51.8 51.8 63.7 63.7 83.7 83.7 104 103.6 128
Maximum input current
Continuous (3x380–440 V) [A] 55 66 66 82 82 96 96 133 133 161
Intermittent (60 s overload) (3x380–
440 V) [A]
82.5 72.6 99 90.2 123 106 144 146 200 177
Continuous (3x441–480 V) [A] 47 59 59 73 73 95 95 118 118 145
Intermittent (60 s overload) (3x441–
480 V) [A]
70.5 64.9 88.5 80.3 110 105 143 130 177 160
Maximum pre-fuses [A] 100 125 160 250 250
Additional specications
Protection rating IP20 maximum
cable cross-section for line power
and motor [mm
2
] ([AWG])
35 (2) 50 (1) 50 (1) 150 (300 MCM) 150 (300 MCM)
Protection rating IP20 maximum
cable cross-section for brake and
load sharing
[mm
2
] ([AWG])
35 (2) 50 (1) 50 (1) 95 (4/0) 95 (4/0)
Protection ratings IP21, IP55, IP66
maximum cable cross-section for
line power and motor
[mm
2
] ([AWG])
50 (1) 50 (1) 50 (1) 150 (300 MCM) 150 (300 MCM)
Protection ratings IP21, IP55, IP66
maximum cable cross-section for
brake and load sharing [mm
2
]
([AWG])
50 (1) 50 (1) 50 (1) 95 (3/0) 95 (3/0)
Maximum cable cross-section
2)
for
line power disconnect
[mm
2
] ([AWG])
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
Estimated power loss
3)
at rated maximum load [W]
4)
570 698 697 843 891 1083 1022 1384 1232 1474
Eciency
5)
0.98 0.98 0.98 0.98 0.99
Table 7.10 Line Power Supply 3x380–480 V AC, P37K–P90K
Specications
Design Guide
MG20N622 Danfoss A/S © 09/2014 All rights reserved. 157
7 7

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals