Binary Outputs
AV0
AV1
AV2
AV4
BV1
BV2
BV3
BV4
BV5
Multistate Outputs
8-04 Control Timeout Function
Option: Function:
Select the time-out function. The time-out function is activated when the control word fails to be
updated within the time period specified in par. 8-03
Control Timeout Time
. Choice [20] only appears
after setting the Metasys N2 protocol.
[0] * Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
[7] Select setup 1
[8] Select setup 2
[9] Select setup 3
[10] Select setup 4
[20] N2 Override Release
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a time-out. This parameter is active
only when par. 8-04
Control Timeout Function
is set to [Set-up 1-4].
[0] Hold set-up Retains the set-up selected in par. 8-04
Control Timeout Function
and displays a warning, until
par. 8-06
Reset Control Timeout
toggles. Then the frequency converter resumes its original set-up.
[1] * Resume set-up Resumes the set-up active prior to the time-out.
8-06 Reset Control Timeout
Option: Function:
This parameter is active only when the choice
Hold set-up
[0] has been selected in par. 8-05
End-
of-Timeout Function
.
[0] * Do not reset Retains the set-up specified in par. 8-04
Control Timeout Function
, [Select setup 1-4] following a
control time-out.
[1] Do reset Returns the frequency converter to the original set-up following a control word time-out. When the
value is set to
Do reset
[1], the frequency converter performs the reset and then immediately reverts
to the
Do not reset
[0] setting.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
103