NB!
Resets parameters selected in Personal Menu with default factory setting.
Par. 14-22
Operation Mode
initialises all except:
Par. 14-50
RFI Filter
Par. 8-30
Protocol
Par. 8-31
Address
Par. 8-32
Baud Rate
Par. 8-35
Minimum Response Delay
Par. 8-36
Maximum Response Delay
Par. 8-37
Maximum Inter-Char Delay
Par. 15-00
Operating Hours
to par. 15-05
Over Volt's
Par. 15-20
Historic Log: Event
to par. 15-22
Historic Log: Time
Par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
Manual initialisation
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
This procedure initializes all except: Par. 15-00
Operating Hours
; par. 15-03
Power Up's
; par. 15-04
Over Temp's
; par. 15-05
Over Volt's
.
NB!
When you carry out manual initialisation, you also reset serial communication, par. 14-50
RFI Filter
and fault log settings.
Removes parameters selected in par. 25-00
Cascade Controller
.
NB!
After initialization and power cycling, the display will not show any information until after a couple of minutes.
2 How to Programme VLT
®
HVAC Drive Programming Guide
30
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
2

Table of Contents

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals