14-12 Function at Mains Imbalance
Option: Function:
Operation under severe main imbalance conditions reduces the lifetime of the motor. Conditions are
considered severe if the motor is operated continuously near nominal load (e.g. a pump or fan
running near full speed).
When a severe mains imbalance is detected:
[0] * Trip Select
Trip
[0] to trip the frequency converter.
[1] Warning Select
Warning
[1] to issue a warning.
[2] Disabled Select
Disabled
[2] for no action.
[3] Derate Select
Derate
[3] for derating the frequency converter.
3.14.4 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling and control card self test or initialisation.
14-20 Reset Mode
Option: Function:
Select the reset function after tripping. Once reset, the frequency converter can be restarted.
[0] * Manual reset Select
Manual reset
[0], to perform a reset via [RESET] or via the digital inputs.
[1] Automatic reset x 1 Select
Automatic reset x 1…x20
[1]-[12] to perform between one and twenty automatic resets after
tripping.
[2] Automatic reset x 2
[3] Automatic reset x 3
[4] Automatic reset x 4
[5] Automatic reset x 5
[6] Automatic reset x 6
[7] Automatic reset x 7
[8] Automatic reset x 8
[9] Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset Select
Infinite Automatic Reset
[13] for continuous resetting after tripping.
NB!
The motor may start without warning. If the specified number of AUTOMATIC RESETs is reached within 10 minutes, the frequency
converter enters Manual reset [0] mode. After the Manual reset is performed, the setting of par. 14-20
Reset Mode
reverts to the
original selection. If the number of automatic resets is not reached within 10 minutes, or when a Manual reset is performed, the internal
AUTOMATIC RESET counter returns to zero.
NB!
Automatic reset will also be active for resetting safe stop function.