1-58 Flystart Test Pulses Current
Range: Function:
30 %* [0 - 200 %] Control the percentage of the magnetizing current. The parameter is active when par. 1-73
Flying
Start
is enabled. This parameter is only available in VVC+.
1-59 Flystart Test Pulses Frequency
Range: Function:
200 %* [0 - 500 %] Control the percentage of the frequency of the test pulses. The parameter is active when
par. 1-73
Flying Start
is enabled. This parameter is only available in VVC+.
3.3.5 1-6* Load Depend. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the % value to compensate voltage in relation to load when the motor is running at low speed
and obtain the optimum U/f characteristic. The motor size determines the frequency range within
which this parameter is active.
Motor size
Change over
0.25 kW - 7.5 kW < 10 Hz
11 kW - 45 kW < 5 Hz
55 kW - 550 kW < 3-4 Hz
1-61 High Speed Load Compensation
Range: Function:
100 %* [0 - 300 %] Enter the % value to compensate voltage in relation to load when the motor is running at high speed
and obtain the optimum U/f characteristic. The motor size determines the frequency range within
which this parameter is active.
Motor size
Change-over
0.25 kW - 7.5 kW > 10 Hz
11 kW - 45 kW < 5 Hz
55 kW - 550 kW < 3-4 Hz