NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-74 "I-Am" Service
Option: Function:
[0] * Send at power-up
[1] Continuously Choose whether the device should send the "I-Am" service message only at power-up or continu-
ously with an interval of approx. 1 min.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
8-75 Initialisation Password
Range: Function:
Application
dependent*
[0 - 0 N/A] Enter the password needed for execution of Drive Re-initialisation from BACnet.
NB!
This parameter is active only when par. 8-30
Protocol
is set to [9]
FC Option
.
3.9.8 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus communication via the FC Port.
8-80 Bus Message Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid telegrams detected on the bus.
8-81 Bus Error Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of telegrams with faults (e.g. CRC fault), detected on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of valid telegrams addressed to the slave, sent by the frequency
converter.
8-83 Slave Error Count
Range: Function:
0 N/A* [0 - 0 N/A] This parameter shows the number of error telegrams, which could not be executed by the frequency
converter.
8-84 Slave Messages Sent
Range: Function:
0 N/A* [0 - 0 N/A]
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark