EasyManuals Logo

Danfoss VLT Programming Guide

Danfoss VLT
315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #68 background imageLoading...
Page #68 background image
3-45 Ramp 1 S-ramp Ratio at Accel. Start
Range: Function:
50 %* [Application dependant] Enter the proportion of the total ramp-up time (par. 3-41
Ramp 1 Ramp up Time
) in which the
acceleration torque increases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks occurring in the application.
3-46 Ramp 1 S-ramp Ratio at Accel. End
Range: Function:
50 %* [Application dependant] Enter the proportion of the total ramp-up time (par. 3-41
Ramp 1 Ramp up Time
) in which the
acceleration torque decreases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
3-47 Ramp 1 S-ramp Ratio at Decel. Start
Range: Function:
50 %* [Application dependant] Enter the proportion of the total ramp-down time (par. 3-42
Ramp 1 Ramp Down Time
) where the
deceleration torque increases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
3-48 Ramp 1 S-ramp Ratio at Decel. End
Range: Function:
50 %* [Application dependant] Enter the proportion of the total ramp-down time (par. 3-42
Ramp 1 Ramp Down Time
) where the
deceleration torque decreases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
3.5.4 3-5* Ramp 2
Choosing ramp parameters, see 3-4*.
3-51 Ramp 2 Ramp Up Time
Range: Function:
Application
dependent*
[Application dependant] Enter the ramp-up time, i.e. the acceleration time from 0 RPM to par. 1-25
Motor Nominal Speed
.
Choose a ramp-up time such that the output current does not exceed the current limit in
par. 4-18
Current Limit
during ramping. See ramp-down time in par. 3-52
Ramp 2 Ramp Down
Time
.
par
. 3 51 =
tacc
×
nnorm
par
. 1 25
ref
rpm
s
3-52 Ramp 2 Ramp Down Time
Range: Function:
Application
dependent*
[Application dependant] Enter the ramp-down time, i.e. the deceleration time from par. 1-25
Motor Nominal Speed
to 0 RPM.
Choose a ramp-down time such that no over-voltage arises in the inverter due to regenerative
operation of the motor, and such that the generated current does not exceed the current limit set
in par. 4-18
Current Limit
. See ramp-up time in par. 3-51
Ramp 2 Ramp Up Time
.
par
.3 52 =
tdec
×
nnorm
par
. 1 25
ref
rpm
s
3-55 Ramp 2 S-ramp Ratio at Accel. Start
Range: Function:
50 %* [Application dependant] Enter the proportion of the total ramp-up time (par. 3-51
Ramp 2 Ramp up Time
) in which the
acceleration torque increases. The larger the percentage value, the greater the jerk compensation
achieved, and thus the lower the torque jerks in the application.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
68
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3

Table of Contents

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals