0-74 DST/Summertime
Option: Function:
Choose how Daylight Saving Time/Summertime should be handled. For manual DST/Summertime
enter the start date and end date in par. 0-76
DST/Summertime Start
and par. 0-77
DST/Summer-
time End
.
[0] * Off
[2] Manual
0-76 DST/Summertime Start
Range: Function:
Application
dependent*
[Application dependant] Sets the date and time when summertime/DST starts. The date is programmed in the format se-
lected in par. 0-71
Date Format
.
0-77 DST/Summertime End
Range: Function:
Application
dependent*
[Application dependant] Sets the date and time when summertime/DST ends. The date is programmed in the format selected
in par. 0-71
Date Format
.
0-79 Clock Fault
Option: Function:
Enables or disables the clock warning, when the clock has not been set or has been reset due to a
power-down and no backup is installed.
[0] * Disabled
[1] Enabled
0-81 Working Days
Array with 7 elements [0] - [6] displayed below parameter number in display. Press OK and step between elements by means of
and
buttons on
the LCP.
Option: Function:
Set for each weekday if it is a working day or a non-working day. First element of the array is
Monday. The working days are used for Timed Actions.
[0] * No
[1] Yes
0-82 Additional Working Days
Array with 5 elements [0] - [4] displayed below parameter number in display. Press OK and step between elements by means of
and
buttons on
the LCP.
Range: Function:
Application
dependent*
[Application dependant] Defines dates for additional working days that normally would be non-working days according to
par. 0-81
Working Days
.
0-83 Additional Non-Working Days
Array with 15 elements [0] - [14] displayed below parameter number in display. Press OK and step between elements by means of
and
buttons
on the LCP.
Range: Function:
Application
dependent*
[Application dependant] Defines dates for additional working days that normally would be non-working days according to
par. 0-81
Working Days
.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
47
3