EasyManua.ls Logo

Danfoss VLT - Drive Information; Operating Data; Operating Hours; Running Hours

Danfoss VLT
315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14-61 Function at Inverter Overload
Option: Function:
Is used in case of steady overload beyond the thermal limits (110% for 60 sec.).
[0] * Trip Choose Trip [0] to make the frequency converter trip and provide an alarm.
[1] Derate Derate [1] to reduce pump speed in order to decrease the load on the power section and allowing
this to cool down.
14-62 Inv. Overload Derate Current
Range: Function:
95 %* [50 - 100 %] Defines the desired current level (in % of rated output current for the frequency converter) when
running with reduced pump speed after load on the frequency converter has exceeded the allowable
limit (110% for 60 sec.).
3.15 Main Menu - Frequency Converter Information - Group 15
3.15.1 15-** Drive Information
Parameter group containing frequency converter information such as operating data, hardware configuration and software versions.
3.15.2 15-0* Operating Data
Parameter group containing operating data e.g. Operating Hours, kWh counters, Power Ups, etc.
15-00 Operating Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the frequency converter has run. The value is saved when the frequency
converter is turned off.
15-01 Running Hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the motor has run. Reset the counter in par. 15-07
Reset Running Hours
Counter
. The value is saved when the frequency converter is turned off.
15-02 kWh Counter
Range: Function:
0 kWh* [0 - 2147483647 kWh] Registering the power consumption of the motor as a mean value over one hour. Reset the counter
in par. 15-06
Reset kWh Counter
.
15-03 Power Up's
Range: Function:
0 N/A* [0 - 2147483647 N/A] View the number of times the frequency converter has been powered up.
15-04 Over Temp's
Range: Function:
0 N/A* [0 - 65535 N/A] View the number of frequency converter temperature faults which have occurred.
15-05 Over Volt's
Range: Function:
0 N/A* [0 - 65535 N/A] View the number of frequency converter overvoltages which have occurred.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
155
3

Table of Contents

Other manuals for Danfoss VLT

Related product manuals