3-11 Jog Speed [Hz]
Range: Function:
Application
dependent*
[Application dependant] The jog speed is a fixed output speed at which the frequency converter is running when the jog
function is activated.
See also par. 3-80
Jog Ramp Time
.
3-13 Reference Site
Option: Function:
Select which reference site to activate.
[0] * Linked to Hand / Auto Use local reference when in Hand mode; or remote reference when in Auto mode.
[1] Remote Use remote reference in both Hand mode and Auto mode.
[2] Local Use local reference in both Hand mode and Auto mode.
NB!
When set to Local [2], the frequency converter will start with this setting again
following a 'power down'.
3-14 Preset Relative Reference
Range: Function:
0.00 %* [-100.00 - 100.00 %] The actual reference, X, is increased or decreased with the percentage Y, set in par. 3-14
Preset
Relative Reference
. This results in the actual reference Z. Actual reference (X) is the sum of the
inputs selected in par. 3-15
Reference 1 Source
, par. 3-16
Reference 2 Source
, par. 3-17
Reference
3 Source
and par. 8-02
Control Source
.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
64