21-62 Ext. 3 Integral Time
Range: Function:
10000.00
s*
[0.01 - 10000.00 s] See par. 21-22
Ext. 1 Integral Time
for details.
21-63 Ext. 3 Differentation Time
Range: Function:
0.00 s* [0.00 - 10.00 s] See par. 21-23
Ext. 1 Differentation Time
for details.
21-64 Ext. 3 Dif. Gain Limit
Range: Function:
5.0 N/A* [1.0 - 50.0 N/A] See par. 21-24
Ext. 1 Dif. Gain Limit
for details.
3.20 Main Menu - Application Functions - Group 22
This group contains parameters used for monitoring VLT HVAC Drive applications.
22-00 External Interlock Delay
Range: Function:
0 s* [0 - 600 s] Only relevant if one of the digital inputs in parameter group 5-1* has been programmed for
External
Interlock
[7]. The External Interlock Timer will introduce a delay after the signal has been removed
from the digital input programmed for External Interlock, before reaction takes place.
22-01 Power Filter Time
Range: Function:
0.50 s* [0.02 - 10.00 s]
3.20.1 22-2* No-Flow Detection
The frequency converter includes functions for detecting if the load conditions in the system allow the motor to be stopped:
*Low Power Detection
*Low Speed Detection
One of these two signals must be active for a set time (par. 22-24
No-Flow Delay
) before selected action takes place. Possible actions to select
(par. 22-23
No-Flow Function
): No action, Warning, Alarm, Sleep Mode.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
201
3