23-53 Energy Log
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with a number of elements equal to the number of counters ([00]-[xx] below parameter
number in display). Press OK and Step between elements by means of
▲
and
▼
buttons on the
Local Control Panel.
Array elements:
Data from latest period is stored in the counter with the highest index.
At power down all counter values are stored and resumed at next power up.
NB!
All counters are automatically reset when changing the setting in par. 23-50
Energy Log Resolution
. At overflow the update of the
counters will stop at maximum value.
NB!
When mounting an Analog I/O MCB 109 option card, a battery back up of the date and time is included.
23-54 Reset Energy Log
Option: Function:
Select
Do reset
[1] to reset all values in the Energy Log counters shown in par. 23-53
Energy Log
.
After pressing OK the setting of the parameter value will automatically change to
Do not reset
[0].
[0] * Do not reset
[1] Do reset