15-93 Modified Parameters
Array [1000]
Range: Function:
0 N/A* [0 - 9999 N/A] View a list of the parameters that have been changed from their default setting. The list ends with
0. Changes may not be visible until up to 30 seconds after implementation.
15-98 Drive Identification
Range: Function:
0 N/A* [0 - 0 N/A]
15-99 Parameter Metadata
Array [23]
Range: Function:
0 N/A* [0 - 9999 N/A] This parameter contains data used by the MCT10 software tool.
3.16 Main Menu - Data Readouts - Group 16
3.16.1 16-** Data Readouts
Parameter group for data read-outs, e.g. actual references, voltages, control, alarm, warning and status words.
3.16.2 16-0* General Status
Parameters for reading the general status, e.g. the calculated reference, the active control word, status.
16-00 Control Word
Range: Function:
0 N/A* [0 - 65535 N/A] View the Control word sent from the frequency converter via the serial communication port in hex
code.
16-01 Reference [Unit]
Range: Function:
0.000 Ref-
erenceFeed-
backUnit*
[-999999.000 - 999999.000 Refer-
enceFeedbackUnit]
View the present reference value applied on impulse or analog basis in the unit resulting from the
configuration selected in par. 1-00
Configuration Mode
(Hz, Nm or RPM).
16-02 Reference [%]
Range: Function:
0.0 %* [-200.0 - 200.0 %] View the total reference. The total reference is the sum of digital, analog, preset, bus, and freeze
references, plus catch-up and slow-down.
16-03 Status Word
Range: Function:
0 N/A* [0 - 65535 N/A] View the Status word sent from the frequency converter via the serial communication port in hex
code.
16-05 Main Actual Value [%]
Range: Function:
0.00 %* [-100.00 - 100.00 %] View the two-byte word sent with the Status word to the bus Master reporting the Main Actual Value.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
163
3

Table of Contents

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals