25-46 Destaging Speed [RPM]
Range: Function:
0 RPM* [0 - 0 RPM] Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump,
in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed.
When the variable speed pump reaches the “Destaging Speed” the fixed speed pump is destaged.
Destaging Speed is calculated based on par. 25-43
Destaging Threshold
, and par. 4-13
Motor Speed
High Limit [RPM]
.
Destaging Speed is calculated with the following formula:
DESTAGE
=
HIGH
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the
value of Destaging Threshold.
25-47 Destaging Speed [Hz]
Range: Function:
0.0 Hz* [0.0 - 0.0 Hz] Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump,
in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed.
When the variable speed pump reaches the “Destaging Speed” the fixed speed pump is destaged.
Destaging Speed is calculated based on par. 25-43
Destaging Threshold
, and par. 4-14
Motor Speed
High Limit [Hz]
.
Destaging Speed is calculated with the following formula:
DESTAGE
=
HIGH
DESTAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
DESTAGE100%
is the value of Destaging Threshold.
3.23.5 25-5* Alternation Settings
Parameters for defining the conditions for alternation of the variable speed pump (lead), if selected as part of the control strategy.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
248
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3

Table of Contents

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)