25-24 SBW Destaging Delay
Range: Function:
15 s* [0 - 3000 s] Immediate destaging of a fixed speed pump is not desirable when a momentary pressure increase
in the system that exceeds the Staging Bandwidth (SBW). Destaging is delayed by the length of
time programmed. If the pressure decreases to within the SBW before the timer has elapsed, the
timer is reset.
25-25 OBW Time
Range: Function:
10 s* [0 - 300 s] Staging a fixed speed pump creates a momentary pressure peak in the system, which might exceed
the Override Bandwidth (OBW). It is not desirable to destage a pump in response to a staging
pressure peak. The OBW Time can be programmed to prevent staging until the system pressure
has stabilized and normal control established. Set the timer to a value that allows the system to
stabilize after staging. The 10 second factory setting is appropriate in most applications. In highly
dynamic systems, a shorter time may be desirable.
25-26 Destage At No-Flow
Option: Function:
The Destage at No-Flow parameter ensures that when a no-flow situation occurs, the fixed speed
pumps will be destaged one-by-one until the no-flow signal disappears. This requires that No Flow
Detection is active. See parameter group 22-2*.
If Destage at No-Flow is disabled the Cascade Controller does not change the normal behavior of
the system.
[0] * Disabled
[1] Enabled
3 Parameter Description VLT
®
HVAC Drive Programming Guide
244
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3

Table of Contents

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals