22-81 Square-linear Curve Approximation
Range: Function:
100 %* [0 - 100 %] Example 1:
Adjustment of this parameter allows the shape of the control curve to be adjusted.
0 = Linear
100% = Ideal shape (theoretical).
NB!
Please note: Not visible when running in cascade.
22-82 Work Point Calculation
Option: Function:
Example 1: Speed at System Design Working Point is known:
From the data sheet showing characteristics for the specific equipment at different speeds, simply
reading across from the H
DESIGN
point and the Q
DESIGN
point allows us to find point A, which is the
System Design Working Point. The pump characteristics at this point should be identified and the
associated speed programmed. Closing the valves and adjusting the speed until H
MIN
has been
achieved allows the speed at the no flow point to be identified.
Adjustment of par. 22-81
Square-linear Curve Approximation
then allows the shape of the control
curve to be adjusted infinitely.
Example 2:
Speed at System Design Working Point is not known: Where the Speed at System Design Working
Point is unknown, another reference point on the control curve needs to be determined by means
of the data sheet. By looking at the curve for the rated speed and plotting the design pressure
3 Parameter Description VLT
®
HVAC Drive Programming Guide
214
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3

Table of Contents

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)

Related product manuals