5-16 Terminal X30/2 Digital Input
This parameter is active when option module MCB 101 is installed in the frequency converter. Same options and functions as par. 5-1* except for
Pulse input
[32].
Option: Function:
[0] * No operation
5-17 Terminal X30/3 Digital Input
This parameter is active when option module MCB 101 is installed in the frequency converter. Same options and functions as par. 5-1* except for
Pulse input
[32].
Option: Function:
[0] * No operation
5-18 Terminal X30/4 Digital Input
This parameter is active when option module MCB 101 is installed in the frequency converter. Same options and functions as par. 5-1* except for
Pulse input
[32].
Option: Function:
[0] * No operation
3.7.4 5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29. Set the
I/O function for terminal 27 in par. 5-01
Terminal 27 Mode
and set the I/O function for terminal 29 in par. 5-02
Terminal 29 Mode
. These parameters
cannot be adjusted while the motor is running.
The digital outputs can be programmed with these functions:
[0] No operation
Default for all digital outputs and relay outputs
[1] Control ready The control board receives supply voltage.
[2] Drive ready The frequency converter is ready for operation and applies a supply signal on the control board.
[3] Drive ready / remote control The frequency converter is ready for operation and is in Auto On mode.
[4] Stand-by / no warning The frequency converter is ready for operation. No start or stop command is been given (start/
disable). There are no warnings.
[5] Running The motor is running.
[6] Running / no warning The output speed is higher than the speed set in par. 1-81
Min Speed for Function at Stop [RPM]
.
The motor is running and there are no warnings.
[8] Run on reference / no warning The motor runs at reference speed.
[9] Alarm An alarm activates the output. There are no warnings.
[10] Alarm or warning An alarm or a warning activates the output.
[11] At torque limit The torque limit set in par. 4-16
Torque Limit Motor Mode
or par. 1-17 has been exceeded.
[12] Out of current range The motor current is outside the range set in par. 4-18
Current Limit
.
[13] Below current, low The motor current is lower than set in par. 4-50
Warning Current Low
.
[14] Above current, high The motor current is higher than set in par. 4-51
Warning Current High
.
[15] Out of speed range The output speed is outside the range set in par. 4-52
Warning Speed Low
and par. 4-53
Warning
Speed High
.
[16] Below speed, low The output speed is lower than the setting in par. 4-52
Warning Speed Low
.
[17] Above speed, high The output speed is higher than the setting in par. 4-53
Warning Speed High
.
[18] Out of feedback range The feedback is outside the range set in par. 4-56
Warning Feedback Low
and par. 4-57
Warning
Feedback High
.
[19] Below feedback low The feedback is below the limit set in par. 4-56
Warning Feedback Low
.
[20] Above feedback high The feedback is above the limit set in par. 4-57
Warning Feedback High
.
[21] Thermal warning The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency
converter, the brake resistor, or the thermistor.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
82