5-58 Term. 33 High Ref./Feedb. Value
Range: Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A] Enter the high reference value [RPM] for the motor shaft speed. See also par. 5-53
Term. 29 High
Ref./Feedb. Value
.
5-59 Pulse Filter Time Constant #33
Range: Function:
100 ms* [1 - 1000 ms] Enter the pulse filter time constant. The low-pass filter reduces the influence on and dampens os-
cillations on the feedback signal from the control.
This is an advantage, e.g. if there is a great amount on noise in the system. This parameter cannot
be adjusted while the motor is running.
3.7.7 5-6* Pulse Outputs
Parameters for configuring the scaling and output functions of pulse outputs. The pulse outputs are designated to terminals 27 or 29. Select terminal 27
output in par. 5-01
Terminal 27 Mode
and terminal 29 output in par. 5-02
Terminal 29 Mode
.
Options for readout output variables:
[0] No operation
[45] Bus ctrl.
[48] Bus ctrl., timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque relative to limit
[105] Torque relative to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[113] Ext. Closed Loop
[114] Ext. Closed Loop
[115] Ext. Closed Loop
Select the operation variable assigned for terminal 27 readouts.