10-23 COS Filter 4
Range: Function:
0 N/A* [0 - 65535 N/A] Enter the value for COS Filter 4 to set up the filter mask for PCD 4. When operating in COS (Change-
Of-State), this function filters out bits in PCD 4 that should not be sent if they change.
3.11.5 10-3* Parameter Access
Parameter group providing access to indexed parameters and defining programming set-up.
10-31 Store Data Values
Option: Function:
Parameter values changed via DeviceNet are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
[0] * Off Deactivates the non-volatile storage function.
[1] Store all setups Stores all parameter values from the active set-up in the non-volatile memory. The selection returns
to Off [0] when all values have been stored.
[2] Store all setups Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
10-33 Store Always
Option: Function:
[0] * Off Deactivates non-volatile storage of data.
[1] On Stores parameter data received via DeviceNet in EEPROM non-volatile memory as default.
3.12 Main Menu - LonWorks - Group 11
3.12.1 LonWorks, 11-**
Parameter group for all LonWorks specific parameters.
Parameters related to LonWorks ID.
11-00 Neuron ID
Range: Function:
0 N/A* [0 - 0 N/A] View the Neuron chip's unique Neuron ID number.
11-10 Drive Profile
Option: Function:
This parameter allows selecting between LONMARK Functional Profiles.
[0] * VSD profile The Danfoss Profile and the Node Object are common for all profiles.
[1] Pump controller
11-15 LON Warning Word
Range: Function:
0 N/A* [0 - 65535 N/A] This parameter contains the LON specific warnings.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
129