[9] * Active Set-up Follows the active set-up selected in par. 0-10
Active Set-up
.
This parameter is unique to LCP and fieldbuses. See also par. 0-11
Programming Set-up
.
9-71 Profibus Save Data Values
Option: Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
[0] * Off Deactivates the non-volatile storage function.
[1] Store all setups Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
[2] Store all setups Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
9-72 ProfibusDriveReset
Option: Function:
[0] * No action
[1] Power-on reset Resets frequency converter upon power-up, as for power-cycle.
[3] Comm option reset Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g.
par. 9-18
Node Address
.
When reset, the frequency converter disappears from the fieldbus, which may cause a communi-
cation error from the master.
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range: Function:
0 N/A* [0 - 9999 N/A] This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range: Function:
0 N/A* [0 - 9999 N/A] This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range: Function:
0 N/A* [0 - 9999 N/A] This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
122
MG.11.C9.02 - VLT
®
is a registered Danfoss trademark
3