Select the correct relay number in output A and output B and enable the function. Change the relay function to limit in the I/O menu.
Then the relay will activate, but no alarm will appear. Note that to avoid an alarm, both output A and output B need to be configured
to a relay.
INFO
If the relay function is not changed to M-Logic / Limit function, an alarm will appear at every running situation.
6.3 Idle running
The purpose of the idle run function is to change the start and stop sequences to allow the genset to operate under low temperature
conditions.
DESIGNER'S HANDBOOK 4189341275A EN Page 104 of 196