EasyManuals Logo

Deif AGC-4 Mk II Designers Handbook

Deif AGC-4 Mk II
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #122 background imageLoading...
Page #122 background image
INFO
Only reset is possible. It is not possible to add an offset to the run hour counter.
6.6.9 Fan priority update
In parameter 6562, the priority update rate (the hours between priority changes) is selected:
If the fan priority update is set to 0 hours, the priority order is: Fan A, Fan B, Fan C, Fan D.
6.7 Derate genset
The derate function reduces the maximum output power of the genset when specific conditions require this. For example, if the
ambient temperature increases so much that the cooling water coolers do not have enough cooling capacity. If the genset is not
derated, there can be alarms and/or a shutdown. Three, independent derate functions are available.
The derating is based on the nominal power.
DESIGNER'S HANDBOOK 4189341275A EN Page 122 of 196

Table of Contents

Other manuals for Deif AGC-4 Mk II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deif AGC-4 Mk II and is the answer not in the manual?

Deif AGC-4 Mk II Specifications

General IconGeneral
BrandDeif
ModelAGC-4 Mk II
CategoryController
LanguageEnglish

Related product manuals