2.9.5 Start-up overview with idle run
1500
300
400
StarterStart
Remove
starter
(0-2000RPM)
800
6351
Running
detection
within
(0-1200 sec)
Idle start
6290
Idle run
6180
Start
prepare
(0-600 sec)
Run coil
(0-600 sec)
6150
Cranking
6160
Run status
(0-300 sec)
2740
Delay of
Regulation
(0-9900 sec)
Running detection level
(0-4000 RPM)
6173
Idle
finished
Frequency
detection level
(20-35 Hz)
6165
Nominal
speed
Remove
starter
6174
Inhibit status: Not running
6160
4560
Hz/V failure
(1-99 sec)
Activate
regulation
1000
Run status
(0-300 sec)
Oil pressure inhibit
The set points and failures in this overview are the same as described in the chapter "Start-up overview", except for the idle run
function. This function is described in the chapter "Idle running".
2.9.6 Stop sequence
The drawings illustrate the stop sequence.
DESIGNER'S HANDBOOK 4189341275A EN Page 58 of 196