2.8.6 MB close sequence
Start
Voltage on
mains/bus
Synchronised
Sync MB
End
No
No
Yes
Is MB open
No
Yes
MB closed
Close failure
alarm
Yes
Yes
GB closed
Yes
No
Alarm sync.
failure
Sync timer
runout
GB open
sequence
Yes
No
Yes
Voltage on
gen
Back sync ON
Close MB
Alarm GB
open failure
Direct close OK
No
Yes
Yes
No
No
No