6.3.4 Temperature-dependent idle start-up
This is an example of how to set up a system that will start up in idle speed, if the coolant temperature is below a specified value.
When the temperature exceeds the specified value, the genset will ramp up to nominal values.
Example
The function is made with delta analogue 1 (menus 4601, 4602 and 4610) and one M-Logic line. After starting, when the coolant
temperature is below 110 degrees, the controller will idle the genset. Once the temperature reaches 110 degrees, the controller will
automatically ramp up to full speed. See the settings below.