2. Functions
2.1 Standard functions
This chapter includes functional descriptions of standard functions as well as illustrations of the relevant application types.
Flowcharts and single-line diagrams will be used in order to simplify the information.
The standard functions are listed in the following paragraphs.
2.1.1 Operation modes
Automatic Mains Failure
Island operation
Fixed power/base load
Peak shaving
Load takeover
Mains power export
2.1.2 Engine control
Start/stop sequences
Run and stop coil
Relay outputs for governor control
2.1.3 Generator protection (ANSI)
2 × reverse power (32)
5 × overload (32)
6 × over-current (50/51)
2 × over-voltage (59)
3 × under-voltage (27)
3 × over-/under-frequency (81)
Voltage-dependent over-current (51V)
Current/voltage unbalance (60)
Loss of excitation/over-excitation (40/32RV)
Non-essential load/load shedding, three levels (I, Hz, P>, P>>)
Multi-inputs (digital, 4 to 20 mA, 0 to 40 V DC, Pt100, Pt1000 or RMI)
Digital inputs
2.1.4 Busbar protection (ANSI)
4 × over-voltage (59)
5 × under-voltage (27)
4 × over-frequency (81)
5 × under-frequency (81)
Voltage unbalance (60)
2.1.5 Display DU-2
Prepared for remote mounting
Push-buttons for start and stop
DESIGNER'S HANDBOOK 4189341275A EN Page 11 of 196