Cummins PCC applications
Figure 6.1 PCC interface to AGC
PCC in the DEIF power management system
If the AGC is part of a power management system, it normally gets load sharing information from the power management system
over CAN bus. You can force an AGC to use the analogue load sharing lines: Activate Output, Command Power management, Use
Ana LS instead of CAN in M-Logic. This allows the Cummins PCC to share the load with the AGCs.
This is useful if the AGC is placed on all gensets only sending start and stop commands to the PCC. This means that the Cummins
ILSI unit is not necessary.
DESIGNER'S HANDBOOK 4189341275A EN Page 115 of 196