Vector group 0
The phase shift is 0 degrees.
Figure 6.6 Yy0 example
1L1
1L21L3
HV side
2L1
2L22L3
LV (generator) side
1L1 to 2L1 phase angle is 0 degrees
Table 6.1
Phase compensation setting
Parameter Function Setting
9141 BB (mains)/generator angle compensation 0 degrees
Figure 6.7 Connections
Busbar
Generator
1L1
1L2
2L2
2L1 LV HV
GB
1L3
2L3
AGC 79 81 83 85 87 89
INFO
The connection shown in the diagram should always be used when an AGC is used for a genset.
Vector group 1
The phase shift is -30 degrees.
DESIGNER'S HANDBOOK 4189341275A EN Page 171 of 196