Example: Parameters for differential measurement 1 inputs
Parameter Name Range Default
4601 Delta ana1 InpA See list below. Multi input 102
4602 Delta ana1 InpB See list below. Multi input 102
The following inputs are possible (depending on the controller options):
• Multi-inputs
◦ 102, 105, 108
• CIO 308
◦ 1.08, 1.11, 1.14, 1.17, 1.20, 1.23, 1.26, 1.29
• EIC measurements (option H12)
◦ Oil pres (SPN 100)
◦ Cooling water temp. (SPN 110), Oil temp. (SPN 175), Ambient temp. (SPN 171), Intercool temp. (SPN 52), Fuel temp. (SPN
174)
◦ Fuel delivery pres. (SPN 94), Air filter1 diff. pres. (SPN 107), Air filter2 diff. pres. (SPN 2809)
◦ Fuel supply pump pres. (SPN 1381), Fuel filter diff. pres. SS (SPN 1382), Oil filter diff. pres. (SPN 99)
◦ T. Exhaust left (SPN 2434), T. Exhaust right (SPN 2433)
◦ Fuel filter diff. pres. (SPN 95)
◦ Percent Load At Current Speed (SPN 92)
◦ T. Winding Highest, T. Winding Lowest, T. Winding 1, T. Winding 2, T. Winding 3
◦ DEF Level (SPN 1761), DEF Temp (SPN 3031)
• External inputs (option H12)
◦ Ext. Ana. In 1 to 8
• Analogue input (option M15.X)
◦ Analogue input 127, 129 131, 133
• Multi-input (M16.X)
◦ Analogue input 127, 129 131, 133
The relevant alarm set point is chosen in parameters 4610-4660, 4680-4730 and 4750-4800. Each alarm can be configured in two
alarm levels for each differential measurement between analogue input A and input B. The screenshot below shows the parameters
to configure an alarm for differential measurement 1.