Electrical specifications
Item Specifications
Power supply to
device in IO-Link
mode or SIO (DI)
mode
Rated voltage
24 VDC (20.4 VDC~ 28.8 VDC) (9-15%~+20%)
Maximum load
current
0.2A/port
Short-circuit
protection
Yes
Digital inputs in
SIO (DI) mode
Internal I/O
common
NPN, PNP
Input voltage /
current
24 VDC, 5 mA
ON voltage
>15 VDC
OFF voltage
<5 VDC
Filter time
0 65 ms (0: no filter)
Digital outputs in
SIO (DO) mode
Internal I/O
common
NPN, PNP
Output voltage /
current
24 VDC (20.4 VDC~ 28.8 VDC), 0.1A/port
Short-circuit
protection
Yes
Leakage current
<0.1 mA
Residual
voltage
<1.5 VDC
Digital inputs for
pin 2 in IO-Link
mode
Internal I/O
common
NPN, PNP
Input voltage /
current
24 VDC, 2 mA
ON voltage
>15 VDC
OFF voltage
<5 VDC
Filter time
0 65 ms (0: no filter)
Electronical isolation
500 VAC
Power consumption
0.8 W
Weight
133g
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage