2.1 General Specifications
Item
Specifications
Operating temperature
-20 to 60°C
Storage temperature
-40 to 80°C
Operating humidity
5–95%
No condensation
Storage humidity
5–95%
No condensation
Work environment
No corrosive gas exists.
Installation location
In a control box
Pollution degree
2
Ingress protection
(IP ratings)
IP20
EMC (electromagnetic
compatibility)
Refer to Appendix C for more information.
Vibration resistance
Tested with:
5 Hz f 8.4 Hz, constant amplitude 3.5 mm;
8.4 Hz f 150 Hz, constant acceleration 1g
Duration of oscillation: 10 sweep cycles
per axis on each direction of the three mutually perpendicular axes
International Standard IEC 61131-2 & IEC 60068-2-6 (TEST Fc)
Shock resistance
Tested with:
Half-sine wave:
Strength of shock 15 g peak value, 11 ms duration;
Shock direction: The shocks in each in direction per axis, on three mutually
perpendicular axes (total of 18 shocks)
International Standard IEC 61131-2 & IEC 60068-2-27 (TEST Ea)
Safety
Conforms to IEC 61131-2, UL508
Ambient air
temperature-barometric
pressure-altitude
Operating: 1080 ~ 795hPa (-1000 ~ 2000 m)
Storage:1080 ~ 660hPa (-1000 ~ 3500 m)
Endurance
Applicable to the removable terminal block, function card slot, SD card slot,
Ethernet port, USB port on the modules and the connecting ports between
modules.
Plugging: more than 100 times (Each plugging in is counted as 1 time and pins
inside the slots or ports should not be bent or crooked.)
Force used for plugging in: to plug in a removalbe terminal block, the force
used is around 70 g and for other slots and ports, the force is around 220 g.
Force used for plugging out: to plug out a removalbe terminal block, the force
used is around 1000 g and for other slots and ports, the force is around 20 g.
UL 94 Flame
Classifications
UL 94 V-0
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
BrandDelta
ModelAS Series
CategoryControl Unit
LanguageEnglish

Related product manuals