If the local CPU module wants to send 10-word data to the remote device, the data will be stored in D0~D9 before the
data is sent. If the local CPU module receives 20-word data from the remote device, the data will be stored in
D100~D119.
If the length of data received is larger than the length set, the first 20-word data will be stored in D100~D119, and the
data after the first 20-word data will be discarded. Likewise, if the length of data received is less than the length set,
the data will be stored in the devices starting from D100, and the values in devices where no new data is stored will be
retained.
If no data is transmitted, and 60 seconds have elapsed, the CPU module will close the socket, and terminate the
connection.
8.2.13 Ethernet Port Advance Setting RTU Mapping
In the
RTU Mapping
table, users can set Delta RTU-EN01 slave in connection with PLC CPU. The remote device can
be controlled via Ethernet. For the setting and operation of RTU-EN01, refer to the operation manual.
Select RTU Mapping Enable checkbox to enable the function of connection between RTU module and PLC CPU. Set
the update cycle in
Cycle
box and a timeout in
Timeout
box. It means a timeout when RTU does not give a reply within
the timeout set.
The data mapping between each group of RTU-EN01 and PLC CPU is set in the
RTU Mapping
section. RTU-EN01
and I/O module connected to it are set via DCISoft. For more information on DCISoft, refer to the operation manual.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage
CertificationsCE, UL

Related product manuals