D.3.2 Periodic Inspection
 
No.  Item  Inspection  Criterion  Remedy 
1 
Ambient environment 
Ambient 
temperature/hu
midity 
The ambient temperature 
and the ambient humidity 
are measured by a 
thermometer and a 
hygrometer. 
The ambient 
temperature and the 
ambient humidity must 
conform to the 
specifications for the 
modules or the 
backplane. If the 
specifications are 
different, the strictest 
specifications have 
priority. 
To ensure that the 
system operates 
in a stable 
environment, 
determine why the 
environment 
varies, and 
resolve the issue. 
Atmosphere  Measure corrosive gas. 
Corrosive gas must 
not be present. 
2  Supply voltage 
Measure the AC power 
supply. 
The power supply 
should meet the 
specifications for the 
power supply module. 
Check the power 
supply. 
3 
Installation 
Looseness 
Check whether the module 
is loose. 
The module must be 
installed firmly. 
Please refer to 
Chapter 4 for 
more information 
on installing the 
module. 
Adhesion of 
dirt 
Check the appearance. 
Dirt must not be 
present. 
Remove the dirt. 
4 
Connection 
Looseness of 
terminal 
screws   
Tighten the screws with a 
screwdriver. 
The screws must not 
be loose. 
Tighten the 
screws. 
Looseness of 
connectors 
Pull the connectors. 
The connectors must 
not be loose. 
Tighten the 
screws on the 
connectors. 
5 
PLC system 
diagnosis 
Check the error logs.  No new error occurs. 
Please refer to 
section 12.1.3 for 
more information. 