Limit 3: You can connect up to 16 analog modules (AD, DA, XA, RTD, TC and LC) to the PLC.
Limit 4: You can connect up to 4 communication modules (AS00SCM, AS01DNET-A, and AS04SIL-A) to
the PLC.
Limit 5: You can connect up to 8 positioning modules (AS02PU-A, AS04PU-A and AS02HC-A) to the PLC.
Limit 6: You can connect up to 15 remote modules (AS00SCM+AS-FCOPM) to the PLC. The remote
modules can work with up to eight digital/analog modules.
Limit 7: You can connect up to 15 remote modules (AS00SCM+AS-FEN02) to the PLC. The remote
modules can work with up to eight digital/analog modules.
Limit 8: You can connect up to 8 extension modules (digital modules, analog modules, temperature
measurement module, etc.) to AS01DNET-A (RTU mode).
Limit 9: You can connect remote modules to digital/analog modules (temperature measurement and load
cell modules), but not to communication or positioning modules.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage
CertificationsCE, UL