A.  General-purpose timer 
When the instruction TMR is executed, the general-purpose timer begins to count. When the value of the 
timer matches the timer setting value, the output coil is ON. 
  When X0.0=ON and the timer takes 100 ms as the timing unit, the output coil T0 is ON when the 
value of the timer = setting value100.   
  When X0.0=OFF or the power is off, the value of the timer is 0 and the output coil T0 is OFF. 
 
 
X0.0
T0(PV)
Y0.0
SV:K100
10
 sec
 
 
B.  Accumulative timer 
When the instruction TMR is executed, the accumulative timer begins to count. When the value of the 
timer matches the timer setting value, the output coil is ON. As long as you add the letter S in front of the 
letter T, the timer becomes an accumulative timer. When the conditional contact is OFF, the value of the 
accumulative timer is not reset. When the conditional contact is ON, the timer counts from the current 
value. 
  When X0.0=ON and the timer T250 takes 100 ms as the timing unit, the output coil T250 is ON 
when the value of the timer = timer setting value100.   
  When X0.0=OFF or the power is off, the timer T250 stops counting, and the value of the timer 
stays the same. When X0.0=ON, the value of the timer is accumulating value When the 
accumulated value = timer setting value 100, the output coil T250 is ON.   