Item / per transmission Specification
AS300
AS200 /
AS100
AS-FEN02 AS-FECAT
Modbus TCP
Maximum connection
quantity for Client *
1
32 16 8 0
Maximum connection
quantity for Server*
1
32 16 8 1
Max. data length
100 words
Socket
(communication
port)*
1
TCP connection quantity
4 2
N/A N/A
UDP connection quantity
Max. data length
200 bytes
SMTP (for
emailing)
Emailing quantity
4 4
*1: Numbering is used for connections via the communication port. You can use connection 1 in TCP mode or UDP
mode and up to 4 connections can be made per transmission. If connection 1 is used in TCP mode, the same connection
number cannot be used in UDP mode.