AS100 Series 
 Model 
AS132P-A 
AS132R-A 
AS148P-A 
AS148R-A 
AS164P-A 
AS164R-A 
100 ~ 240VAC (-15% ~ 10%); 50 / 60Hz ± 5% 
140 A (@264VAC,I
2
t = 29.4 A
2
S) 
130 VA
MAX
 
Internal power     
  consumption (W) 
2.64  3.84  3  4.8  3.36  5.76 
500 mA 
  circuit protection 
Yes 
3,000 VAC (Primary-secondary); 3,000 VAC (Primary-FE); 500 VAC (Secondary-FE) 
Insulation voltage
Above 5 MΩ 
The voltage between all inputs/outputs and the ground is 500 VAC. 
Ground 
The diameter of the ground should not be less than the diameters of the 
cables connected to the terminals L and N. 
Communication 
port isolation   
USB, COM1, COM2, and CAN ports: 500 VAC 
Ethernet: 1500 VAC 
 
 
  AS300 Series: Electrical specifications for the inputs on digital input/output module. The signals 
passing through the inputs are 24 VDC signals. 
Model
AS332T-A 
AS320T-B 
AS324MT-A 
16 (X0.0-X0.15)  8 (X0.0-X0.7)  12 (X0.0-X0.11) 
Terminal connector 
MIL connector 
Removable spring-type 
MIL connector 
Input form 
Direct current (sinking or sourcing) 
X0.0+–X0.3+/X0.0- to 
X0.3-: differential input 
X0.4–X0.11: Direct current 
Input voltage/ 
current 
24 VDC 
5 mA 
–X0.3+/X0.0- to X0.3-:
 
Action 
level 
OFF→ON
>15 VDC 
X0.0+–X0.3+/X0.0- to X0.3-
>0.2VDC 
ON→OFF
<5 VDC 
X0.0+–X0.3+/X0.0- to 
X0.3-: <-0.2VDC 
time 
OFF→ON
X0.0~X0.11: < 2.5μs 
X0.12~X0.15: < 50μs 
X0.0+–X0.3+/X0.0- to 
X0.3-:  < 0.125 μs 
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com 
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com