6.  Codes displayed in SR825 when the AS Series PLC is the slave:   
 
0  Working normally 
N/A 
Note: When the heartbeat alam function is not 
activated, if the connection is normal before a 
disconnection occurs, the code for the slave will 
still be working normally after the connection is 
AS Series PLC is being initialized. 
A1  AS Series PLC is pre-operational. 
Check if the CANopen bus cable is properly 
connected. If the master communication is not 
activated, no handling is needed. 
A3 
The data are being downloaded to 
Wait to finish downloading the configured data. 
B0  Heartbeat message time-out 
Check if the CANopen bus cable is properly 
B1 
PDO data length returned from the 
slave is not consistent with the 
length set in the node list. 
Reset the PDO data length in the slave and 
download the new setting to the AS
 Series PLC. 
F4  BUS-OFF state is detected. 
Check if the CANopen bus cables are properly 
connected and ensure that all the node devices run 
at the same baud rate before you reboot. 
FB 
The sending buffer in the AS Series 
Check if the CANopen bus cable is properly 
connected and then reboot. 
FC 
The receiving buffer in the AS Series 
Check if the CANopen bus cable is properly 
connected and then reboot. 
 
   