code
Description
CPU
status
ERROR LED indicator
ON
Blinking
fast
Blinking
normally
Blinking
slowly
OFF
19E7 Timeout on the slave error control Continue V
19E8 The node IDs of master and slave are duplicated. Continue V
19F3 Error in the configuration Continue V
19F4 CANopen communication is in the BUS-OFF state.
Continue V
19FB The sending registers exceed the range. Continue V
19FC The receiving registers exceed the range. Continue V
2001
Not
using the FCOMP card or not in the right mode
for the ASDA-
A2 while using the CANopen
communication instruction.
Continue V
2003
The device used in the program excee
ds the device
range or is illegal.
Continue V
200A
Invalid instruction
Stop
V
200B
The operand n or the other constant operands K/H
exceed the range.
Continue V
200C The operands overlap. Continue V
200D
The binary to binary-coded decimal conversion
is
incorrect.
Continue V
200E
The string does not end with 00.
Continue
V
2012
Incorrect division operation
Continue
V
2013
The value exceeds the range of values which can
be represented by the floating-point numbers.
Continue V
2014
The task designated by the TKON or YKOFF
instruction is incorrect, or exceeds the range.
Continue V
2017
The instruction BREAK is written outside of the
FOR-NEXT loop.
Continue V
2027
No such position planning table number or the
format is incorrect.
Continue V
2028
The high speed output instruction is being
executed. Only one instruction can be executed at
a time.
Continue V
2030
During the execution of CSFO instruction, the
output frequency exceeds the upper limit.
Continue V
2031
During the execution of CSFO instruciotn, when
the output frequency is set to 0, but even after 2
seconds, the output is still not complete.
Continue V
6004 The IP address filter is set incorrectly. Continue V
600D
RJ45 port is not connected.
Continue
V
6010
The number of MODBUS TCP connections
exceeds the range.
Continue V
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage
CertificationsCE, UL

Related product manuals