Analog-to-Digital
Conversion
Current Input
Rated Input Range
±20 mA
0 mA20 mA
4 mA20 mA
Rated Conversion
Range
K-32000
~
K+2000
K0
~
K32000
K0
~
K32000
Hardware Input
Limit*
1
-20.24 mA ~ 20.24 mA -0.24 mA ~ 20.24 mA 3.81 mA ~ 20.19 mA
Conversion Limit*
2
K-32384
~
K32384
K-384
~
K32384
K-384
~
K32384
Error Rate
Room Temperature: ±0.2% ; Full Temperature Range: ±0.5%
Hardware Resolution
16 bits
Input Impedance
250Ω
Absolute Input
Range*
3
±32 mA
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input
signal is below the lower limit, it only shows the minimum value. And an error flag will be set.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion
limit error appears. For example in the voltage input mode (4 mA to 20 mA), when the input signal is 0 mA,
exceeding the hardware upper limit, it also exceeds the conversion upper limit. The module uses the upper
limit value (-384) as the input signal and a conversion limit error appears.
*3: If an input signal exceeds the absolute range, it might damage the channel.
Functional specifications for the digital-to-analog conversion
Digital-to-Analog
Conversion
Voltage Output
Rated Output Range
±10 V
0 ~ 10 V
±5 V
0 ~ 5 V 1 ~ 5 V
Conversion Range
K-32000
~
K32000
K0
~
K32000
K-32000
~
K32000
K0
~
K32000
K0
~
K32000
Hardware Output Range
-10.1 V
~
+10.1 V
-0.1 V
~
10.1 V
-5.05 V
~
+5.05 V
-0.05 V
~
+5.05 V
0.95
~
5.05 V
Error Rate
(Room Temperature)
±0.2%
Error Range
(Full temperature range)
±0.5%
Linearity Error
(Room Temperature)
±0.05%
Linearity Error
(Full Temperature Range)
±0.05%
Hardware Resolution
12 bits
Permissible load
impedance
1k Ω 500Ω
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com

Table of Contents

Other manuals for Delta AS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS Series and is the answer not in the manual?

Delta AS Series Specifications

General IconGeneral
SeriesAS Series
Power Supply24VDC
Cooling MethodNatural convection
Programming LanguageFunction Block Diagram (FBD)
Communication InterfaceEthernet, RS-232, RS-485
Output Voltage24V DC
Output Current2A
Operating Temperature55°C
Storage Temperature70°C
Protection FeaturesOvervoltage
CertificationsCE, UL