The electronic braking is not available when operang from supply voltages above 24 V d.c.
+10%.
When operang from supply voltages below 24 V d.c. +10%, the electronic braking opon may
be enabled to reduce the pump deceleraon me and to recover some energy from the pump.
This is achieved by returning power from the pump to the electrical supply. The rate at which
electrical energy is returned to the supply is regulated so as to limit the supply voltage to 24 V
d.c. +10%. In order to achieve the fastest electronic braking mes there must be somewhere
for the returned power to go, such as:
• A supply capable of receiving the returned power
• Other devices sharing the 24 V d.c. bus with the pump
• A load resistor of approximately 10 Ω switched across the 24 V d.c. supply when
decelerang the pump
Logic interface
The motor controller can only be operated through the logic interface. There are three types
signals on the logic interface.
The signal types are:
• Control inputs: these are switch-type signals that are used to control the pump
• Status outputs: these outputs
idenfy the status of the system
• Analogue output: this provides a 0 – 10 V output for a number of pump parameters
The logic interface has been designed to support both serial and parallel control and
monitoring, operang through one connector. For serial control either RS232 (default) or RS485
can be selected using the RS485/RS232 slide switch located on the motor controller (refer to
Connecon for serial control and monitoring on page 28).
The logic interface can be plugged directly into the Edwards TIC Turbo Controller, TIC Turbo
Instrument Controller or TAG Controller and then use the funconality that they provide.
Alternavely, the logic interface can be connected to the customer control system.
For more informaon about the logic interface, refer to Logic interface connector on page 91.
USB interface
The USB service port is designed to work in conjuncon with Edwards nST PC soware. The
primary purpose of this interface is to allow easy conguraon of the nEXT85 pump.
Some operaonal capabilies are provided, including START/STOP to enable pump operaonal
checks to be made via the USB service port. However it is not intended as an industrial control
interface for unaended machine to machine (M2M) control.
The USB service port will support communicaons concurrently with the serial interface in the
logic interface connector. This enables the pump status and logs to be reviewed, and the pump
to be congured while the pump is installed and running.
The USB service port should only be used when the 24 - 48 V d.c. power is applied. Use of the
USB service port without 24 - 48 V d.c. power risks corrupon of the pump controller memory.
Parallel control and monitoring
The simple parallel interface is a quick and easy way to control the pump.
This is the same interface used on
exisng 24 V Edwards Turbo Pumps. The controls that are
available to use are start and standby. The system status can be monitored using the normal,
fail and analogue output signals.
B8G0-00-880A - Overview of the nEXT85
Page 16