Device Functions Proline Promass 83 FOUNDATION Fieldbus 3 Transducer Block
Endress+Hauser 115
System Value -
Volume Flow
read only Use this parameter to view the volume flow.The volume flow is derived
from the measured mass flow and the measured density of the fluid.
Display:
5-digit floating-point number, including unit and sign
(e.g. 5.5445 dm
3
/min; 1.4359 m
3
/h; –731.63 gal/d; etc.)
System Unit -
Volume Flow
AUTO - OOS Use this parameter to select the unit for the volume flow (volume/time).
The unit you select here is also valid for:
• Simulation
• Low flow cut off
Options:
Metric:
Cubic centimeter → cm
3
/s; cm
3
/min; cm
3
/h; cm
3
/day
Cubic decimeter → dm
3
/s; dm
3
/min; dm
3
/h; dm
3
/day
Cubic meter → m
3
/s; m
3
/min; m
3
/h; m
3
/day
Milliliter → ml/s; ml/min; ml/h; ml/day
Liter → l/s; l/min; l/h; l/day
Hectoliter → hl/s; hl/min; hl/h; hl/day
Megaliter → Ml/s; Ml/min; Ml/h; Ml/day
US:
Cubic centimeter → cc/s; cc/min; cc/h; cc/day
Acre foot → af/s; af/min; af/h; af/day
Cubic foot → ft
3
/s; ft
3
/min; ft
3
/h; ft
3
/day
Fluid ounce → oz f/s; oz f/min; oz f/h; oz f/day
Gallon → gal/s; gal/min; gal/h; gal/day
Kilo gallon → Kgal/s; Kgal/min; Kgal/h; Kgal/day
Million gallon → Mgal/s; Mgal/min; Mgal/h; Mgal/day
Barrel (normal fluids: 31.5 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Barrel (beer: 31.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Barrel (petrochemicals: 42.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Barrel (filling tanks: 55.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Imperial:
Gallon → gal/s; gal/min; gal/h; gal/day
Mega gallon → Mgal/s; Mgal/min; Mgal/h; Mgal/day
Barrel (beer: 36.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Barrel (petrochemicals: 34.97 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Factory setting:
Depends on nominal diameter and country → Page 193 ff.
! Note!
The unit selected here has no influence on the transmitted process variable
to the Analog Input function block.
System Value -
Corr.Volume Flow
read only The calculated corrected volume flow appears on the display. The calculated
corrected volume flow is derived from the measured mass flow and the
reference density of the fluid (density at reference temperature, measured or
fixed entry).
Display:
5-digit floating-point number, including unit and sign
(e.g. 1.3549 Nm
3
/h; 7.9846 scm/day; etc.)
"Flow" Transducer Block / base index 1400:
Parameter
Write access
with operating
mode
(MODE_BLK)
Description