Chapter 5: Installation
EST3X Technical Reference Manual 101
UL 864 notification appliance circuit (NAC)
signal synchronization
Table 25 lists the installation requirements for systems that must meet UL 864
NAC signal synchronization requirements.
Table 25: Installation requirements for UL 864 signal synchronization
Circuit
Installation requirements
PS10
-4B NACs Emergency evacuation signals are synchronized with main b
oard
signaling line circuits on a “per cabinet” basis when you
configure the NACs as a Genesis device type and use Genesis
or Enhanced Integrity notification appliances.
SFS1
-CPU Main Board
signaling line circuits
Emergency evacuation signals are synchronized with PS10-4B
NACs on a “per cabinet” basis when you use SIGA-CC1S or
SIGA-MCC1S modules configured for auto-sync output
(personality code 25) and Genesis or Enhanced Integrity
notification appliances.
3-SSDC(1) and 3-SDDC(1) modules:
Emergency evacuation signals are synchronized on a “per
loop” basis when you use SIGA-CC1S or SIGA-MCC1S
modules (personality code 25) and Genesis or Enhanced
Integrity notification appliances.
Emergency evacuation signals are synchronized on a “per
module” basis when you use SIGA-CC1 or SIGA-MCC1
modules (personality code 5), G1M or G1M-RM Genesis
Signal Master modules, and Genesis notification appliances.
3
-AADC Emergency evacuation signals are synchronized on a “per
circuit” basis when you use G1M or G1M-RM Genesis Signal
Master modules, and Genesis notification appliances.
3
-IDC8/4 Emergency evacuation signals are synchronized on a “per
circuit” basis when you use G1M or G1M-RM Genesis Signal
Master modules, and Genesis notification appliances. See
Figure 20 on page 103 for typical wiring.
SIGA
-CC1, SIGA-MCC1,
SIGA
-CC1S, and
SIGA
-MCC1S
Signature CC1 modules do not generate temporal signals, they
simply turn the NAC circuit on or off. You must configure the
notification appliances for temporal or steady output as desired.
3
-ZA20 and 3-ZA40
amplifier modules
Emergency evacuation signals are synchronized on a “per
circuit” basis when you use G1M or G1M-RM Genesis Signal
Master modules, and Genesis notification appliances.